Item |
15kV data |
25kV data |
35kV data |
|
Continuous operating voltage |
8.7kV/14.4kV |
15.2kV 26.3kV |
26kV/35kV |
|
AC withstand voltage |
45kV/1min |
55kV/5min |
117kV/5min |
|
DC withstand voltage |
53kV/15min |
78kV/15m in |
104kV |
|
1.5/50 μs Im pulse with stand voltage |
95kV |
125kV |
215kV |
|
Partial discharge voltage |
13kV |
22kV |
45kV |
|
Item |
200AMP |
600AMP |
|
Load operating current |
Available in 14.4kV and 200A 10 times under breaking and closed operation |
|
|
Fault closed current |
Available in 14.4kV, 1000N0.175 1 time under by fault closed operation |
|
|
Heat stable current |
16kA 1s |
30kA 2s |
|
Peak withstand current |
10kA |
105kA |
| Reference No. | Conductor cross section(mm²) | Stretch range over insulation(mm) |
| AH TT 24/600-35 |
35 |
18.6 |
| AH TT 24/600-50 |
50 |
19.6 |
| AH TT 24/600-70 |
70 |
21 |
| AH TT 24/600-95 |
95 |
22.6 |
| AH TT 24/600-120 |
120 |
24.2 |
| AH TT 24/600-150 |
150 |
25.6 |
| AH TT 24/600-185 |
185 |
27.2 |
| AH TT 24/600-240 |
240 |
28.7 |
| AH TT 24/600-300 |
300 |
31.1 |
| AH TT 24/600-400 |
400 |
33.2 |