Conditions of Application:
Ambient environment:
- Temperature:-40ºC≤T≤-40ºC
- Altitude above sea level:≤1000m
- Max.wind speed:≤35m/s
- Earthquake intensity:≤8 degree
| Type |
Rated Voltage(kv) |
Rated current (A) |
Breaking
current
(A) |
Impulse
Voltage(kv) |
Power-frequeny
withsand voltage( kV) |
Creepage distance (mm) |
Weight(kg) |
Dimensions (cm) |
| AH-19 |
24-27 |
100 |
10,000 |
150 |
65 |
560 |
7 |
51×34×14.5 |
| 24-27 |
200 |
12,000 |
150 |
65 |
560 |
7 |
51×34×14.5 |
| AH-20 |
24-27 |
100 |
8,000 |
150 |
50 |
530 |
12 |
48 .5 ×34. 5×15 |
| 24-27 |
200 |
10,000 |
150 |
50 |
530 |
12 |
48.5 ×34. 5×15 |
| AH-21 |
24-27 |
100 |
8,000 |
150 |
65 |
520 |
12 |
48 ×34. 5 ×14 |
| 24-27 |
200 |
10,000 |
150 |
65 |
520 |
12 |
48 ×34. 5 ×14 |